A recently finalized revision to the ibc model building code limits the size of fire protective glazing such as safety wired glass and safety ceramic used within vision panels for 60 or 90 minute temperature rise doors to no more than 100 square inches whether or not sprinklers are present.
Maximum glass size for one hour fire rated door.
Sidelites and transoms around a 20 minute fire door in a 1 hour exit require a 45 minute fire rating with hose stream.
3 hour doors are not permitted to have fire protection rated glass.
Maximum glass light size for a 90 minute 1 1 2 hour door depends on the type of glass being installed.
Wire glass 100 square inches is max exposed glass when wire glass is used.
To increase the amount of fire rated glass in 60 or 90 minute temperature rise doors and still meet code you must use fire resistive glazing that meets astm e119.
Ul 9 nfpa 252 can 4 s104 astm e119 larr 25798 ul 10b nfpa 257 can 4 s106 ul 10c openings with doors maximum width 12 6 3 81 m maximum height including transom 10 11 7 8 3 35 m 45 minute openings without doors maximum width 12 7 1 2 3 84 m maximum height 10 1 3 07 m minimum wall thickness 3 3 4 095 m.
Frame tests performed in accordance with.
Inches with no dimension exceed ing 10 inches.
Maximum glass light size for a 90 minute 1 1 2 hour door depends on the type of glass being installed.
There is a problem with the unqualified statement fire ratings up to 3 hours and here s why.
Fire resistance rated glazing in excess of 100 sq inches 0 065m2 shall be permitted in fire door assemblies when tested as components of the door assemblies and not as glass lights and shall have the maximum end temperature rise of 450 degrees f 250 degrees c in accordance with 716 5 5.
45 minute fire protective windows are permitted in a 1 hour exit corridor up to a maximum of 25 of the wall area.
What is the maximum glass light size on a 90 min 1 1 2 hour fire rated door.
Wire glass 100 square inches is max exposed glass when wire glass is used.
Limits the size of fire protection rated glass such as safety wired glass and safety glass ceramic used in 60 and 90 minute doors to 100 sq.
20 45 minute doors still require fire protection rated glass up to the maximum.
Maximum glass light size for a 90 minute 1 1 2 hour door depends on the type of glass being installed.
While it is true that ceramics a fire protective glazing product are listed up to 3 hours it is purposely.
If a designer wishes to use more glazing then 1 hour fire resistive glazing like superlite ii xl 60 should be used to meet code requirements.
Wire glass 100 square inches is max exposed glass when wire glass is used.
When the code requires fire doors rated 1 hour or more then the sidelites and transoms around that door must be fire resistive and rated to the same standard as the wall itself e g 1 or 2 hour.
If the door serves as a horizontal exit door in a fire wall it is further restricted to 100 sq.